{"created":"2021-03-01T06:07:45.242336+00:00","id":3973,"links":{},"metadata":{"_buckets":{"deposit":"507bf564-4311-48d3-a6cf-47c32d81ecaa"},"_deposit":{"id":"3973","owners":[],"pid":{"revision_id":0,"type":"depid","value":"3973"},"status":"published"},"_oai":{"id":"oai:niigata-u.repo.nii.ac.jp:00003973","sets":["453:454","468:469:470"]},"item_5_alternative_title_1":{"attribute_name":"その他のタイトル","attribute_value_mlt":[{"subitem_alternative_title":"STUDY ON CONVECTIVE, RADIANT AND TOTAL HEAT TRANSFER COEFFICIENT IN RADIANT ENVIRONMENT AND CONDENSATION CONTROL TECHNIQUE IN THE CASE OF FLOOR COOLING"}]},"item_5_biblio_info_6":{"attribute_name":"書誌情報","attribute_value_mlt":[{"bibliographicIssueDates":{"bibliographicIssueDate":"2006-03","bibliographicIssueDateType":"Issued"},"bibliographicPageEnd":"28","bibliographicPageStart":"21","bibliographicVolumeNumber":"601","bibliographic_titles":[{"bibliographic_title":"日本建築学会環境系論文集"},{"bibliographic_title":"日本建築学会環境系論文集","bibliographic_titleLang":"en"}]}]},"item_5_description_4":{"attribute_name":"抄録","attribute_value_mlt":[{"subitem_description":"This study is composed of two parts. One is the measurement results of the convective, radiant and total heat transfer coefficient, and the other is the study of condensation control technique in the case of floor cooling. Two studies are tested by the environment test chamber, which controls the each surfaces temperature of the floor, wall and ceiling, using cold and warm water radiation panel. The results of the measurement are as follows: (1) Both vertical and horizontal temperature distribution is 21-22℃ when floor heating, and the temperature distribution is uniform. (2) The temperature differences by the heating air conditioner are larger than by floor heating. (3) The radiant heat transfer of the floor is the 19.3W/m^2 in case of floor surface temperature sets 40℃, the ceiling and walls temperature set 30℃. (4) The calculating method to prevent condensation at cooling floor is made by parameters of temperature of dehumidification coil entrance water and the area of heat exchanger.","subitem_description_type":"Abstract"}]},"item_5_full_name_3":{"attribute_name":"著者別名","attribute_value_mlt":[{"nameIdentifiers":[{"nameIdentifier":"46483","nameIdentifierScheme":"WEKO"}],"names":[{"name":"Hasegawa, Hiroshi"}]},{"nameIdentifiers":[{"nameIdentifier":"46484","nameIdentifierScheme":"WEKO"}],"names":[{"name":"Akabayashi, Shin-ichi"}]},{"nameIdentifiers":[{"nameIdentifier":"46485","nameIdentifierScheme":"WEKO"}],"names":[{"name":"Sakaguchi, Jun"}]}]},"item_5_publisher_7":{"attribute_name":"出版者","attribute_value_mlt":[{"subitem_publisher":"日本建築学会"}]},"item_5_rights_15":{"attribute_name":"権利","attribute_value_mlt":[{"subitem_rights":"社団法人日本建築学会"}]},"item_5_select_19":{"attribute_name":"著者版フラグ","attribute_value_mlt":[{"subitem_select_item":"publisher"}]},"item_5_source_id_11":{"attribute_name":"書誌レコードID","attribute_value_mlt":[{"subitem_source_identifier":"AA11830377","subitem_source_identifier_type":"NCID"}]},"item_5_source_id_9":{"attribute_name":"ISSN","attribute_value_mlt":[{"subitem_source_identifier":"13480685","subitem_source_identifier_type":"ISSN"}]},"item_creator":{"attribute_name":"著者","attribute_type":"creator","attribute_value_mlt":[{"creatorNames":[{"creatorName":"長谷川, 弘"}],"nameIdentifiers":[{"nameIdentifier":"46480","nameIdentifierScheme":"WEKO"}]},{"creatorNames":[{"creatorName":"赤林, 伸一"}],"nameIdentifiers":[{"nameIdentifier":"46481","nameIdentifierScheme":"WEKO"}]},{"creatorNames":[{"creatorName":"坂口, 淳"}],"nameIdentifiers":[{"nameIdentifier":"46482","nameIdentifierScheme":"WEKO"}]}]},"item_files":{"attribute_name":"ファイル情報","attribute_type":"file","attribute_value_mlt":[{"accessrole":"open_date","date":[{"dateType":"Available","dateValue":"2019-07-30"}],"displaytype":"detail","filename":"ZF_601_21-28.pdf","filesize":[{"value":"1.1 MB"}],"format":"application/pdf","licensetype":"license_note","mimetype":"application/pdf","url":{"label":"ZF_601_21-28.pdf","url":"https://niigata-u.repo.nii.ac.jp/record/3973/files/ZF_601_21-28.pdf"},"version_id":"f4aa0080-0066-4e68-9f9c-bb888df28872"}]},"item_keyword":{"attribute_name":"キーワード","attribute_value_mlt":[{"subitem_subject":"Environmental test chamber","subitem_subject_scheme":"Other"},{"subitem_subject":"Radiation","subitem_subject_scheme":"Other"},{"subitem_subject":"Convection heat-transfer coefficient","subitem_subject_scheme":"Other"},{"subitem_subject":"Total heat-transfer coefficient","subitem_subject_scheme":"Other"},{"subitem_subject":"Condensation","subitem_subject_scheme":"Other"},{"subitem_subject":"環境試験室","subitem_subject_scheme":"Other"},{"subitem_subject":"放射","subitem_subject_scheme":"Other"},{"subitem_subject":"対流熱伝達率","subitem_subject_scheme":"Other"},{"subitem_subject":"総合熱伝達率","subitem_subject_scheme":"Other"},{"subitem_subject":"結露","subitem_subject_scheme":"Other"}]},"item_language":{"attribute_name":"言語","attribute_value_mlt":[{"subitem_language":"jpn"}]},"item_resource_type":{"attribute_name":"資源タイプ","attribute_value_mlt":[{"resourcetype":"journal article","resourceuri":"http://purl.org/coar/resource_type/c_6501"}]},"item_title":"放射環境における対流・放射・総合熱伝達率の測定結果と床冷房時の結露防止手法に関する研究","item_titles":{"attribute_name":"タイトル","attribute_value_mlt":[{"subitem_title":"放射環境における対流・放射・総合熱伝達率の測定結果と床冷房時の結露防止手法に関する研究"},{"subitem_title":"放射環境における対流・放射・総合熱伝達率の測定結果と床冷房時の結露防止手法に関する研究","subitem_title_language":"en"}]},"item_type_id":"5","owner":"1","path":["454","470"],"pubdate":{"attribute_name":"公開日","attribute_value":"2012-06-05"},"publish_date":"2012-06-05","publish_status":"0","recid":"3973","relation_version_is_last":true,"title":["放射環境における対流・放射・総合熱伝達率の測定結果と床冷房時の結露防止手法に関する研究"],"weko_creator_id":"1","weko_shared_id":null},"updated":"2022-12-15T03:36:59.322978+00:00"}